The main objective of a Fire Alarm System is to detect hazardous scenarios that could damage life, property and resources such as a fire, an explosion, a chemical spill or radiation. It becomes a herculean task to identify and suppress a fire in real-time for any organization without a perpetual fire monitoring and detection system.

Matrix PROPAC Conventional Fire Alarm Panel (CFAP) is a powerful and proactive CFAP, intelligently designed to satisfy all the fire safety requirements for apartments, offices or industries. Its state-of-the-art technology ensures identification of the smallest smoldering event that makes it vital for providing real time response to prevent human and property loss.

Interface Diagram

Interface Diagram

  • Zones or IDC (Initiating Device Circuits): 2, 4 and 8
  • Support for 32 detectors per zone
  • Sounders or NAC (Notification Appliance Circuits): 2 and 4
  • Integration with third party devices using Fire & Fault Relay
  • Aux In for directly activating the NACs
  • Ethernet port for Easy Configuration and Events Download remotely
  • Support for 32 Mimic Panels on RS-485

Salient Features of the CFAP

Preventive Maintenance
Various tests available for evaluating the functionality of the system from time-to-time
  • Zone & NAC Disable: For disabling the zones or NACs that need repair
  • Walk Test: For testing the zones for a programmable time internal
  • Sounder Test: For testing the Sounder Circuit
  • Lamp Test: For testing the user interface LEDs

Easy Integration
  • Easy integration with third party relay based devices using fire and fault relay
  • Integration with access control devices, water sprinkler, PA/VA system, gas release panels, etc.
  • Integration with third party repeaters like Mimic panel and other annunciators through RS485

Web Configuration through Ethernet
  • User friendly web configuration tool called Jeeves
  • Easy and quick configuration
  • Downloadable Events log file in readable format

Interactive User Interface
  • User Friendly, Interactive, LCD Display based Menu User can configure below features from menu
  • 33 Status LEDs to view fire and fault events distinctly
  • Evacuate, Reset, Silent and Ack/Mute control keys
  • User menu containing all important functionalities like status check, maintenance, configuration, system restore, etc

Advanced Fault Detection
  • Detection of 9 different general, zone and sounder circuit faults
  • Alerts to user via audio visual indicators
  • Fault relay on any fault event to integrate for third party use

Panic Prevention
  • Delayed mode in case of fire event by delaying activation of sounders
  • Configurable as per users requirement
  • Applicable in sensitive areas like hospitals, server rooms, pharmaceutical companies, etc.

User Access Levels and Codes
  • 4 different password protected user access levels
  • Level based rights to different users to access different functions
  • Access control for panel safety and security

Events Log
  • Maintenance log of up to 999 events
  • Alarm, Fault and Admin Events
  • Downloadable in readable format from computer through Ethernet


Conventional Fire Alarm Panel


Models Description Notification Circuits
PROPAC CFAP2 2 Zone Conventional Fire Alarm Panel 2
PROPAC CFAP4 4 Zone Conventional Fire Alarm Panel 2
PROPAC CFAP8 8 Zone Conventional Fire Alarm Panel 4

Technical Specifications

System Configuration 2,4 and 8 Zones Panel
Terminal Capacity 1 mm2 to 2.5 mm2 Solid or Standard Wire
Power Supply
Mains 100-265 VAC, 47-63 Hz
Consumption 60W Max
System Voltage 24 V Nominal, (19-28) VDC
Battery 24 V, 2×12 V @ 3.5 Ah Sealed Lead Acid
Battery Charge Voltage 27.6V Max
Battery Charge Current 0.65A Max
Maximum Current Drawn from Batteries (mains failed) 1.5 A Max
Standby Operation on Fully Charged Battery 24 Hours in Standby and 10 Minutes in Alarm State
Initiating Device Circuit
Zone Circuits 2/4/8
Zone Voltage 20-28 VDC
Current limited <40 mA Max
No of Detectors per Zone 32
Cable type Fire Resistant Screened (FRS) Cable, Minimum Conductor Size 2 mm2
Wiring Style - Y ( Class - B )
Notification Appliance Circuit
Notification Appliance Circuit(NAC) 2/4
Output Voltage 20-28 VDC
Output Current 1A Max per NAC
Maximum no of Bells @ 25 mA 40 Polarized
Maximum no of Electronic Sounders @ 20 mA 50 Polarized
Connection Screw Type Terminal Block, Maximum Conductor Size 2 mm2
Cable Type Fire Resistant Screened Cable, Recommended Conductor Size 2 mm2
Relay and Auxiliary Input Port
FireRelay Form C Relay, 2A@30VDC Max (Resistive)
Fault Relay Form C Relay, 2A@30VDC Max (Resistive)
Auxiliary Input Short to Trigger, 20-28 VDC
Auxiliary Output Port
Auxiliary DC Output 28 VDC @ 150 mA Max
Max Open Circuit Voltage 27.2VDC
Max Sink Current 150mA
Protection Overload Protected, Power Limited
RS485 For Mimic Panel or Annunciator
Ethernet 10/100 Mbps for Programming and Controlling
User Interface and Display
Ethernet based Interface Web Connectivity via On-board Web Server
User Interface Touch SensitiveKeypad
Display 2×24 Characters Alpha Numeric LCD with Backlight
Indicators and Controls
LED Indicators 33 Colored Status Indicators Zonal Alarm,
Zonal Fire/Fault, Power, Fire, Fault, Mains Fault, Battery Fault, Battery Low, Sounder Fault, Ground Fault, System Fault, Delayed Mode, Walk Test, Zone Disable, Sounder Disable, Evacuate, Silence, Ack/Mute
Special Keys Accept, Evacuate, Silence, Ack/Mute, Reset
Access Levels 4
Dimensions (W×H×D) 315 × 280 × 93 mm (12.40” × 11.02” × 3.66”)
Weight 2 Kgs (4.4 lbs) without Batteries
Operating Temperature 0 °C to +50 °C (+32 °F to +122 °F)
Relative Humidity 5-95% RH (Non-Condensing)